product

Flameproof (Type 'd') Isolators


Application
Flameproof isolators are intended for use in areas made potentially hazardous by the presence of flammable liquids, gases or vapours (Zone 1 or Zone 2).
For installation at petroleum refineries, chemical and petrochemical plants and other process industries where a similar hazard exists.
For isolation of electrical equipment up to 300A.

Features

  • Full Certificate of Conformity for Group IIA, IIB and IIC areas.
  • Enclosures used are from EJB (EExd IIB) and GUB (EExd IIC) ranges.
  • Interlocked padlockable handle (padlock not supplied).
  • ISO Metric entries as standard. Other thread entries available on request.
  • Hinges fitted as standard.

Material
Body and cover    Standard: Copper free aluminium alloy LM25 (BS 1490)
Optional: Cast iron ISO 185:1998

Cover Bolts    Standard: Steel zinc plated. 
Optional : Stainless steel.

Finish
Standard: Two coat of Gray oven baked.
Optional : Two pack epoxy paint, or electrostatic powder coated.

Approvals
CENELEC Standards
EN 50014 / 50018
ISSeP Certificate of Conformity:
For EJB Enclosures: 96D.103.1239 EExd-IIB T5
For GUB Enclosures: 96D.103.1242 EExd-IIC T5

Protection Grade
IP 54 - Application of an approved non-hardening grease will give added resistance to the ingress of dust and moisture.
-IP65/66

Entries & thread Standards
Thread forms available are ISO metric 965.1 with 1.5 mm pitch, NPT ANSI B1.20.1,ISO 228.1 (G), or DIN 40430 (PG)

Options
Mounting brackets and screws.
Stainless steel bolts. Expoy paint or electrostatic powder coated.
Cast Iron body and cover.

Earthing
All enclosures are supplied complete with a 6 mm2 internal and external earth stud as standard.

.Mounting
For EJB enclosures, mounting is by four blind holes drilled and tapped in back of enclosure. For GUB enclosures mounting holes are a part of enclosure. Mounting brackets are also available as an optional extra, see 'Options'.

Ordering Information
A range of 2, 3 and 4 pole isolators up to 300 A complete with interlock padlockable handel is available.
Please specify No. of pole and isolator rating when ordering.



Rating Cat. No. Entries
Up to 40A FPT 01 2 x M25
Up to 63A
FPT 02 2 x M32
Up to 80A FPT 03 2 x M40
Up to 125A
FPT 04 2 x M40
Up to 200A FPT 05 2 x M40
Up to 300A FPT 06 2 x M50