Cable Glands

NMG X21 Explosion Proof Non-Armoured Cable Gland


BS 6121 Type A2

  • Dual certification EEx 'd' Flameproof and EEx 'e' Increased Safety helps reduce specification errors.
  • For non-armoured, elastomer and plastic insulated cables.
  • Outdoor or indoor, IP66.
  • Provides a seal on outer sheath of cable.
  • High pull out resistant seal on the cable sheath.

  • Operating Temperature Range
    -50 oC to +100 oC

  • Materials and Finishes
    Manufactured as standard in brass.
    Alternative materials and plating are available upon request.

  • Optional Accessories
    Lead seal for lead sheathed cables.
    Locknut, Sealing Washer, Earthtag, Shroud.

  • Certification and Approvals
    ISSeP certificate No. ISSeP04ATEX052
    EEx 'd' and EEx 'e' . EN 50014, EN 50018 and EN 50019.
    Suitable for use in Zone 1 and Zone 2 , Group IIA, IIB and IIC.

NMG X21
Explosion Proof Non-Armoured Cable Gland BS 6121 Type A2




Explosionproof Outdoor / Indoor, armoured / non-armoured, seal : outer

CABLE GLAND SELECTION TABLE
GLAND
SIZE
REF.
ENTRY THREAD
SIZE
CABLE OUTHER SHEATH 'P'
Approx
HEXAGON
METRIC INCH* MIN MAX   ACROSS
FLATS
ACROSS
CORNERS
Oss** M20 1/2 3.0 6.0 26 25.0 27.5
Os** M20 1/2 3.0 8.0 26 25.0 27.5
O** M20 1/2 7.5 11.9 26 25.0 27.5
A M20 3/4 11.0 14.3 27 30.0 34.5
B M25 1 13.0 20.2 30 36.0 41.5
C M32 1 1/4 19.0 26.5 32 48.0 53.0
C2 M40 1 1/2 25.0 32.5 33 55.0 63.5
D M50 2 31.5 44.4 54 65.0 75.0
E M63 2 1/2 42.5 56.3 54 80.0 92.5
F M75 3 54.5 68.2 56 95.0 109.5

All metric entry threads are 1.5 mm pitch medium fit.
all Dimensions are in millimeters ( except * )
** Sizes Oss, Os and O are also available in M16. For O size with M16 maximum inner sheath is 10.9
ORDERING EXAMPLE: Gland type / Size / Thread, e.g. NMG X21 / A / M20